CVE-2022-1797mediumCWE-400

CVE-2022-1797: medium-severity vulnerability in Rockwell Automation Compact GuardLogix 5370…

Rockwell Automation Logix Controllers Uncontrolled Resource Consumption

Published · Updated

E-mail alert when it lands in KEV, gets a public PoC or its score goes up.

13Vexday Risk Score

No sign of exploitation. No public exploitation artifact known so far.

ssvc Trackcvss 6.8epss 2.2%
A malformed Class 3 common industrial protocol message with a cached connection can cause a denial-of-service condition in Rockwell Automation Logix Controllers, resulting in a major nonrecoverable fault. If the target device becomes unavailable, a user would have to clear the fault and redownload the user project file to bring the device back online.
CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:C/C:N/I:N/A:H