CVE-2013-2806: fallo en Rockwell Automation RSLinx Enterprise Software
Publicada el · Actualizada el
Aviso por correo cuando entre en el KEV, tenga PoC pública o suba de nota.
3Vexday Risk Score
Sin señal de explotación. Ningún artefacto público de explotación conocido hasta ahora.
ssvc Trackepss 3.9%
Rockwell Automation RSLinx Enterprise Software (LogReceiver.exe) CPR9, CPR9-SR1, CPR9-SR2, CPR9-SR3, CPR9-SR4, CPR9-SR5, CPR9-SR5.1, and CPR9-SR6 does not handle input correctly and results in a logic error if it calculates an incorrect value for the “End of Current Record” field. By sending a datagram to the service over Port 4444/UDP with the “Record Data Size” field modified to a specifically oversized value, the service will calculate an undersized value for the “Total Record Size.” Then the service will calculate an incorrect value for the “End of Current Record” field causing access violations that lead to a service crash. The service can be recovered with a manual reboot. The patches and details pertaining to these vulnerabilities can be found at the following Rockwell Automation security advisory link (login is required): https://rockwellautomation.custhelp.com/app/answers/detail/a_id/537599
Productos afectados
Rockwell Automation · RSLinx Enterprise SoftwareCVEs relacionadas — Rockwell Automation RSLinx Enterprise Software
En el mismo producto, de las más peligrosas a las menos.