CVE-2020-11639highCWE-924

CVE-2020-11639: fallo de gravedad alta en ABB Advant MOD 300 AdvaBuild

Insufficient access control on Inter process communication,

Publicada el · Actualizada el

Aviso por correo cuando entre en el KEV, tenga PoC pública o suba de nota.

21Vexday Risk Score

Sin señal de explotación. Ningún artefacto público de explotación conocido hasta ahora.

ssvc Trackcvss 7.8epss 0.1%
An attacker could exploit the vulnerability by injecting garbage data or specially crafted data. Depending on the data injected each process might be affected differently. The process could crash or cause communication issues on the affected node, effectively causing a denial-of-service attack. The attacker could tamper with the data transmitted, causing the product to store wrong information or act on wrong data or display wrong information. This issue affects Advant MOD 300 AdvaBuild: from 3.0 through 3.7 SP2. For an attack to be successful, the attacker must have local access to a node in the system and be able to start a specially crafted application that disrupts the communication. An attacker who successfully exploited the vulnerability would be able to manipulate the data in such way as allowing reads and writes to the controllers or cause Windows processes in 800xA for MOD 300 and AdvaBuild to crash.
CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H