CVE-2022-2081highCWE-787

CVE-2022-2081: fallo de gravedad alta en Hitachi Energy RTU500 series CMU firmware

Publicada el · Actualizada el

Aviso por correo cuando entre en el KEV, tenga PoC pública o suba de nota.

21Vexday Risk Score

Sin señal de explotación. Ningún artefacto público de explotación conocido hasta ahora.

ssvc Trackcvss 7.5epss 0.6%
A vulnerability exists in the HCI Modbus TCP function included in the product versions listed above. If the HCI Modbus TCP is enabled and configured, an attacker could exploit the vulnerability by sending a specially crafted message to the RTU500 in a high rate, causing the targeted RTU500 CMU to reboot. The vulnerability is caused by a lack of flood control which eventually if exploited causes an internal stack overflow in the HCI Modbus TCP function.
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H