CVE-2025-11786highCWE-121

CVE-2025-11786: fallo de gravedad alta en SGE-PLC1000 SGE-PLC50 Circutor

Stack-based buffer overflow vulnerability in Circutor SGE-PLC1000/SGE-PLC50

Publicada el

Aviso por correo cuando entre en el KEV, tenga PoC pública o suba de nota.

21Vexday Risk Score

Sin señal de explotación. Ningún artefacto público de explotación conocido hasta ahora.

ssvc Trackcvss 8.5epss 0.4%
Stack-based buffer overflow vulnerability in Circutor SGE-PLC1000/SGE-PLC50 v9.0.2. In the 'SetUserPassword()' function, the 'newPassword' parameter is directly embedded in a shell command string using 'sprintf()' without any sanitisation or validation, and then executed using 'system()'. This allows an attacker to inject arbitrary shell commands that will be executed with the same privileges as the application.
CVSS:4.0/AV:A/AC:L/AT:N/PR:L/UI:N/VC:H/VI:L/VA:H/SC:H/SI:L/SA:H