CVE-2025-41669highCWE-347

CVE-2025-41669: fallo de gravedad alta en Phoenix Contact AXC F 1152

Insufficient Verification of Data Authenticity

Publicada el

Aviso por correo cuando entre en el KEV, tenga PoC pública o suba de nota.

21Vexday Risk Score

Sin señal de explotación. Ningún artefacto público de explotación conocido hasta ahora.

ssvc Trackcvss 8.7epss 0.2%
The Web-based Management allows a remote low privileged Engineer user to install additional APPs on the device downloaded from the PLCnext Store without implementing any data verification mechanism, leading to the capability for an Engineer user to reach arbitrary code execution with root privileges on the PLC device. A successful exploitation may allow to install a manipulated APP package, potentially impacting integrity and availability of the PLCnext Control.
CVSS:4.0/AV:N/AC:L/AT:N/PR:L/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N