CVE-2013-2805: falha em Rockwell Automation RSLinx Enterprise Software
Publicada em · Atualizada em
Aviso por e-mail quando ela entrar no KEV, ganhar PoC pública ou subir de nota.
3Vexday Risk Score
Sem sinal de exploração. Nenhum artefato público de exploração conhecido até agora.
ssvc Trackepss 3.9%
Rockwell Automation RSLinx Enterprise Software (LogReceiver.exe) CPR9, CPR9-SR1, CPR9-SR2, CPR9-SR3, CPR9-SR4, CPR9-SR5, CPR9-SR5.1, and CPR9-SR6 does not handle input correctly and results in a logic error if it receives a datagram with an incorrect value in the “Record Data Size” field. By sending a datagram to the service over Port 4444/UDP with the “Record Data Size” field modified to an oversized value, an attacker could cause an out-of-bounds read access violation that leads to a service crash. The service can be recovered with a manual reboot. The patches and details pertaining to this vulnerability can be found at the following Rockwell Automation Security Advisory link (login is required): https://rockwellautomation.custhelp.com/app/answers/detail/a_id/537599
Produtos afetados
Rockwell Automation · RSLinx Enterprise SoftwareCVEs relacionadas — Rockwell Automation RSLinx Enterprise Software
No mesmo produto, das mais perigosas para as menos.