CVE-2015-5374
82Vexday Risk Score
Corrija agora. Ela exploração observada pelo VulnCheck e tem exploit funcional público.
ssvc Actepss 74%
da publicação à arma942 dias
Publicada no NVD18 de jul.
1ª PoC+942d
VulnCheck+695d
probabilidade de exploração
74%top 1% das CVEs
exploração observada
simVulnCheck
4 exploit(s) público(s)
A vulnerability has been identified in Firmware variant PROFINET IO for EN100 Ethernet module : All versions < V1.04.01; Firmware variant Modbus TCP for EN100 Ethernet module : All versions < V1.11.00; Firmware variant DNP3 TCP for EN100 Ethernet module : All versions < V1.03; Firmware variant IEC 104 for EN100 Ethernet module : All versions < V1.21; EN100 Ethernet module included in SIPROTEC Merging Unit 6MU80 : All versions < 1.02.02. Specially crafted packets sent to port 50000/UDP could cause a denial-of-service of the affected device. A manual reboot may be required to recover the service of the device.
Produtos afetados
n/a · n/aPoCs públicas encontradas — 4
exploitdbwww.exploit-db.com/exploits/44103não verificadogithubgithub.com/can/CVE-2015-5374-DoS-PoC★ 3cve_referencewww.exploit-db.com/exploits/44103/não verificadovulncheckvulncheck.com/xdb/03c7ec0c65d3não verificado⚠ Recursos públicos, para você avaliar a exposição de sistemas que controla ou está autorizado a testar. Teste apenas com autorização.
Referências
https://ics-cert.us-cert.gov/advisories/ICSA-15-202-01https://ics-cert.us-cert.gov/advisories/ICSA-17-187-03https://www.exploit-db.com/exploits/44103/https://www.siemens.com/cert/pool/cert/siemens_security_advisory_SSA-323211.pdfhttp://www.securityfocus.com/bid/75948http://www.siemens.com/innovation/pool/de/forschungsfelder/siemens_security_advisory_ssa-732541.pdf