CVE-2016-9338: falha em Rockwell Automation MicroLogix 1100 and 1400
Publicada em · Atualizada em
Aviso por e-mail quando ela entrar no KEV, ganhar PoC pública ou subir de nota.
3Vexday Risk Score
Sem sinal de exploração. Nenhum artefato público de exploração conhecido até agora.
ssvc Trackepss 2.4%
An issue was discovered in Rockwell Automation Allen-Bradley MicroLogix 1100 controller 1763-L16AWA, Series A and B, Version 14.000 and prior versions; 1763-L16BBB, Series A and B, Version 14.000 and prior versions; 1763-L16BWA, Series A and B, Version 14.000 and prior versions; and 1763-L16DWD, Series A and B, Version 14.000 and prior versions. Because of an Incorrect Permission Assignment for Critical Resource, users with administrator privileges may be able to remove all administrative users requiring a factory reset to restore ancillary web server function. Exploitation of this vulnerability will still allow the affected device to function in its capacity as a controller.
Produtos afetados
n/a · Rockwell Automation MicroLogix 1100 and 1400