Rockwell Automation ISaGRAF5 Runtime Relative Path Traversal
28Vexday Risk Score
Sem sinal de exploração. Nenhum artefato público de exploração conhecido até agora.
ssvc Trackcvss 9.1epss 6.4%
probabilidade de exploração
6.4%top 7% das CVEs
exploração observada
nãonenhuma fonte reporta
Some commands used by the Rockwell Automation ISaGRAF Runtime Versions 4.x and 5.x eXchange Layer (IXL) protocol perform various file operations in the file system. Since the parameter pointing to the file name is not checked for reserved characters, it is possible for a remote, unauthenticated attacker to traverse an application’s directory, which could lead to remote code execution.
CVSS:3.1/AV:N/AC:L/PR:H/UI:N/S:C/C:H/I:H/A:H
Produtos afetados
Rockwell Automation · ISaGRAF RuntimeReferências
https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2021-159-04https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1131699https://www.cisa.gov/uscert/ics/advisories/icsa-20-280-01https://www.xylem.com/siteassets/about-xylem/cybersecurity/advisories/xylem-multismart-rockwell-isagraf.pdf