CVE-2022-28613: falha de alta gravidade em Hitachi Energy RTU500 series CMU Firmware
Specially Crafted Modbus TCP Packet Vulnerability in RTU500 series
Publicada em · Atualizada em
Aviso por e-mail quando ela entrar no KEV, ganhar PoC pública ou subir de nota.
21Vexday Risk Score
Sem sinal de exploração. Nenhum artefato público de exploração conhecido até agora.
ssvc Trackcvss 7.5epss 1.0%
A vulnerability exists in the HCI Modbus TCP function included in the product versions listed above. If the HCI Modbus TCP is en-abled and configured, an attacker could exploit the vulnerability by sending a specially crafted message to the RTU500, causing the receiving RTU500 CMU to reboot. The vulnerability is caused by the validation error in the length information carried in MBAP header in the HCI Modbus TCP function.
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
Produtos afetados
Hitachi Energy · RTU500 series CMU FirmwareCVEs relacionadas — Hitachi Energy RTU500 series CMU Firmware
No mesmo produto, das mais perigosas para as menos.