CVE-2023-5768: falha de média gravidade em Hitachi Energy RTU500 series
Publicada em · Atualizada em
Aviso por e-mail quando ela entrar no KEV, ganhar PoC pública ou subir de nota.
13Vexday Risk Score
Sem sinal de exploração. Nenhum artefato público de exploração conhecido até agora.
ssvc Trackcvss 5.9epss 0.4%
A vulnerability exists in the HCI IEC 60870-5-104 that affects the RTU500 series product versions listed below.
Incomplete or wrong received APDU frame layout may
cause blocking on link layer. Error reason was an endless blocking when reading incoming frames on link layer
with wrong length information of APDU or delayed reception
of data octets.
Only communication link of affected HCI IEC 60870-5-104
is blocked. If attack sequence stops the communication to
the previously attacked link gets normal again.
CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:N/I:N/A:H
Produtos afetados
Hitachi Energy · RTU500 seriesCVEs relacionadas — Hitachi Energy RTU500 series