CVE-2026-110021: falha de média gravidade em Phoenix Contact PLCnext Engineer
Missing GSDX SignatureValue verification
Publicada em
Aviso por e-mail quando ela entrar no KEV, ganhar PoC pública ou subir de nota.
13Vexday Risk Score
Sem sinal de exploração. Nenhum artefato público de exploração conhecido até agora.
ssvc Trackcvss 6.9epss 0.1%
PLCnext Engineer checks GSDX manifest reference digests but does not cryptographically verify the XML `SignatureValue` over canonicalized `SignedInfo`. An unauthenticated local attacker can modify signed GSDML content, update its manifest digest, retain the public certificate data, and leave an invalid nonempty `SignatureValue`. PLCnext Engineer prior to 2026.6 reports the package as `Valid` and selects the modified device description for import under the default policy.
CVSS:4.0/AV:L/AC:L/AT:N/PR:N/UI:N/VC:N/VI:H/VA:N/SC:N/SI:N/SA:N
Produtos afetados
Phoenix Contact · PLCnext EngineerCVEs relacionadas — Phoenix Contact PLCnext Engineer
No mesmo produto, das mais perigosas para as menos.