CVE-2019-6831
3Vexday Risk Score
No sign of exploitation. No public exploitation artifact known so far.
ssvc Trackepss 1.4%
exploitation probability
1.4%top 29% of all CVEs
observed exploitation
nono source reports it
A CWE-754: Improper Check for Unusual or Exceptional Conditions vulnerability exists in BMXNOR0200H Ethernet / Serial RTU module (all firmware versions), which could cause disconnection of active connections when an unusually high number of IEC 60870- 5-104 packets are received by the module on port 2404/TCP.
Affected products
Schneider Electric SE · BMXNOR0200H Ethernet / Serial RTU module