CVE-2021-32986criticalCWE-288

CVE-2021-32986: critical vulnerability in Automation Direct CLICK PLC CPU Modules: C0-1x…

Automation Direct CLICK PLC CPU Modules Authentication Bypass Using an Alternate Path or Channel

Published · Updated

E-mail alert when it lands in KEV, gets a public PoC or its score goes up.

28Vexday Risk Score

No sign of exploitation. No public exploitation artifact known so far.

ssvc Trackcvss 9.8epss 1.1%
After Automation Direct CLICK PLC CPU Modules: C0-1x CPUs with firmware prior to v3.00 is unlocked by an authorized user, the unlocked state does not timeout. If the programming software is interrupted, the PLC remains unlocked. All subsequent programming connections are allowed without authorization. The PLC is only relocked by a power cycle, or when the programming software disconnects correctly.
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H