CVE-2023-4346highunder attackCWE-645

CVE-2023-4346: high-severity vulnerability in KNX Protocol Connection Authorization Option 1

Published · Updated

E-mail alert when it lands in KEV, gets a public PoC or its score goes up.

51Vexday Risk Score

Prioritize patching. It under exploitation confirmed by CISA.

ssvc Actcvss 7.5epss 1.4%
from disclosure to weapon
Published on NVDAug 29
CISA KEV+1051d
Action required by CISAfederal deadline: 2026-07-29

Apply mitigations in accordance with vendor instructions, ensuring compliance with CISA’s BOD 26-04 Prioritizing Security Updates Based on Risk (see URL in Notes) guidance and CISA’s “Forensics Triage Requirements” (see URL in Notes). Follow applicable BOD 26-04 guidance for cloud services or discontinue use of the product if mitigations are unavailable. Stakeholders are responsible for evaluating each asset's internet exposure and ensuring adherence to BOD 26-04 patching guidelines.

In short

KNX devices using Connection Authorization Option 1 can be permanently locked by setting a BCU password that cannot be reset, leaving users unable to access their own devices. An attacker with network or physical access can exploit this to lock devices remotely or in person.

Technical detail

KNX devices supporting Connection Authorization Option 1 lack secure password reset mechanisms, allowing attackers with network or physical access to set an irreversible BCU key that locks legitimate users out. The vulnerability affects implementations without additional security options, and exploitation requires no authentication on unsecured KNX networks or physical device access.

Summary generated and translated by AI from the official description.

The full analysis of this CVE is available in Portuguese →

KNX devices that use KNX Connection Authorization and support Option 1 are, depending on the implementation, vulnerable to being locked and users being unable to reset them to gain access to the device. The BCU key feature on the devices can be used to create a password for the device, but this password can often not be reset without entering the current password. If the device is configured to interface with a network, an attacker with access to that network could interface with the KNX installation, purge all devices without additional security options enabled, and set a BCU key, locking the device. Even if a device is not connected to a network, an attacker with physical access to the device could also exploit this vulnerability in the same way.
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H