Micro820®, Micro850®, Micro870® – Specialized Fuzzing Vulnerabilities
21Vexday Risk Score
No sign of exploitation. No public exploitation artifact known so far.
ssvc Trackcvss 8.7epss 0.3%
exploitation probability
0.3%top 72% of all CVEs
observed exploitation
nono source reports it
A security issue exists due to improper handling of malformed CIP packets during fuzzing. The controller enters a hard fault with solid red Fault LED and becomes unresponsive. Upon power cycle, the controller will enter recoverable fault where the MS LED and Fault LED become flashing red and reports fault code 0xF019. To recover, clear the fault.
CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N
Affected products
Rockwell Automation · Micro820®, Micro850®, Micro870®