Inductive Automation Ignition Execution with Unnecessary Privileges
21Vexday Risk Score
No sign of exploitation. No public exploitation artifact known so far.
ssvc Trackcvss 7.3epss 0.2%
exploitation probability
0.2%top 88% of all CVEs
observed exploitation
nono source reports it
The vulnerability affects Ignition SCADA applications where Python
scripting is utilized for automation purposes. The vulnerability arises
from the absence of proper security controls that restrict which Python
libraries can be imported and executed within the scripting environment.
The core issue lies in the Ignition service account having system
permissions beyond what an Ignition privileged user requires. When an
authenticated administrator uploads a malicious project file containing
Python scripts with bind shell capabilities, the application executes
these scripts with the same privileges as the Ignition Gateway process,
which typically runs with SYSTEM-level permissions on Windows.
Alternative code execution patterns could lead to similar results.
CVSS:4.0/AV:A/AC:H/AT:N/PR:H/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N
Affected products
Inductive Automation · Ignition