Rockwell Automation Micro800 Vulnerability
28Vexday Risk Score
No sign of exploitation. No public exploitation artifact known so far.
ssvc Trackcvss 9.3epss 0.4%
exploitation probability
0.4%top 70% of all CVEs
observed exploitation
nono source reports it
A security issue exists due to improper handling of malformed CIP Forward Close packets during fuzzing. The controller enters a solid red Fault LED state and becomes unresponsive. Upon power cycle, the controller will enter recoverable fault where the MS LED and Fault LED become flashing red and reports fault code 0xF015. To recover, clear the fault.
CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N
Affected products
Rockwell Automation · PLC - Micro850 L50E