CVE-2025-3498criticalCWE-306

CVE-2025-3498: fallo crítico en Radiflow iSAP Smart Collector

Unauthenticated modification of Radiflow iSAP Smart Collector configuration

Publicada el

Aviso por correo cuando entre en el KEV, tenga PoC pública o suba de nota.

28Vexday Risk Score

Sin señal de explotación. Ningún artefacto público de explotación conocido hasta ahora.

ssvc Trackcvss 9.9epss 0.3%
An unauthenticated user with management network access can get and modify the Radiflow iSAP Smart Collector (CentOS 7 - VSAP 1.20) configuration. The device has two web servers that expose unauthenticated REST APIs on the management network (TCP ports 8084 and 8086). An attacker can use these APIs to get access to all system settings, modify the configuration and execute some commands (e.g., system reboot).
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:C/C:L/I:H/A:L