CVE-2025-3498criticalCWE-306

CVE-2025-3498: falha crítica em Radiflow iSAP Smart Collector

Unauthenticated modification of Radiflow iSAP Smart Collector configuration

Publicada em

Aviso por e-mail quando ela entrar no KEV, ganhar PoC pública ou subir de nota.

28Vexday Risk Score

Sem sinal de exploração. Nenhum artefato público de exploração conhecido até agora.

ssvc Trackcvss 9.9epss 0.3%
An unauthenticated user with management network access can get and modify the Radiflow iSAP Smart Collector (CentOS 7 - VSAP 1.20) configuration. The device has two web servers that expose unauthenticated REST APIs on the management network (TCP ports 8084 and 8086). An attacker can use these APIs to get access to all system settings, modify the configuration and execute some commands (e.g., system reboot).
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:C/C:L/I:H/A:L