CVE-2026-3611criticalCWE-306

CVE-2026-3611: fallo crítico en Honeywell IQ3

Honeywell IQ4x BMS Controller Missing authentication for critical function

Publicada el · Actualizada el

Aviso por correo cuando entre en el KEV, tenga PoC pública o suba de nota.

28Vexday Risk Score

Sin señal de explotación. Ningún artefacto público de explotación conocido hasta ahora.

ssvc Trackcvss 10epss 6.3%
The Honeywell IQ4x building management controller, exposes its full web-based HMI without authentication in its factory-default configuration. With no user module configured, security is disabled by design and the system operates under a System Guest (level 100) context, granting read/write privileges to any party able to reach the HTTP interface. Authentication controls are only enforced after a web user is created via U.htm, which dynamically enables the user module. Because this function is accessible prior to authentication, a remote user can create a new account with administrative read/write permissions enabling the user module and imposing authentication under attacker-controlled credentials. This action can effectively lock legitimate operators out of local and web-based configuration and administration.
CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:H/SI:H/SA:H