CVE-2026-3611: falha crítica em Honeywell IQ3
Honeywell IQ4x BMS Controller Missing authentication for critical function
Publicada em · Atualizada em
Aviso por e-mail quando ela entrar no KEV, ganhar PoC pública ou subir de nota.
28Vexday Risk Score
Sem sinal de exploração. Nenhum artefato público de exploração conhecido até agora.
ssvc Trackcvss 10epss 6.3%
The Honeywell IQ4x building management controller, exposes its full web-based HMI without authentication in its factory-default configuration. With no user module configured, security is disabled by design and the system operates under a System Guest (level 100) context, granting read/write privileges to any party able to reach the HTTP interface. Authentication controls are only enforced after a web user is created via U.htm, which dynamically enables the user module. Because this function is accessible prior to authentication, a remote user can create a new account with administrative read/write permissions enabling the user module and imposing authentication under attacker-controlled credentials. This action can effectively lock legitimate operators out of local and web-based configuration and administration.
CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:H/SI:H/SA:H