← voltar
CVE-2025-9041highCWE-1287

Rockwell Automation FLEX 5000 I/O - Module Fault

21Vexday Risk Score

Sem sinal de exploração. Nenhum artefato público de exploração conhecido até agora.

ssvc Trackcvss 8.7epss 0.3%
probabilidade de exploração
0.3%top 75% das CVEs
exploração observada
nãonenhuma fonte reporta
A security issue exists due to improper handling of CIP Class 32’s request when a module is inhibited on the 5094-IF8 device. It causes the module to enter a fault state with the Module LED flashing red. Upon un-inhibiting, the module returns a connection fault (Code 16#0010), and the module cannot recover without a power cycle.