Rockwell Automation FLEX 5000 I/O - Module Fault
21Vexday Risk Score
No sign of exploitation. No public exploitation artifact known so far.
ssvc Trackcvss 8.7epss 0.3%
exploitation probability
0.3%top 75% of all CVEs
observed exploitation
nono source reports it
A security issue exists due to improper handling of CIP Class 32’s request when a module is inhibited on the 5094-IF8 device. It causes the module to enter a fault state with the Module LED flashing red. Upon un-inhibiting, the module returns a connection fault (Code 16#0010), and the module cannot recover without a power cycle.
CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N
Affected products
Rockwell Automation · FLEX 5000 I/O