CVE-2025-40944
21Vexday Risk Score
Sin señal de explotación. Ningún artefacto público de explotación conocido hasta ahora.
ssvc Trackcvss 8.7epss 0.4%
probabilidad de explotación
0.4%top 62% de las CVE
explotación observada
noninguna fuente lo reporta
A vulnerability has been identified in SIMATIC ET 200AL IM 157-1 PN (6ES7157-1AB00-0AB0) (All versions), SIMATIC ET 200MP IM 155-5 PN HF (6ES7155-5AA00-0AC0) (All versions >= V4.2.0), SIMATIC ET 200SP IM 155-6 MF HF (6ES7155-6MU00-0CN0) (All versions), SIMATIC ET 200SP IM 155-6 PN HA (incl. SIPLUS variants) (All versions < V1.3), SIMATIC ET 200SP IM 155-6 PN R1 (6ES7155-6AU00-0HM0) (All versions < V6.0.1), SIMATIC ET 200SP IM 155-6 PN/2 HF (6ES7155-6AU01-0CN0) (All versions >= V4.2.0 < V4.2.5), SIMATIC ET 200SP IM 155-6 PN/3 HF (6ES7155-6AU30-0CN0) (All versions < V4.2.2), SIMATIC PN/MF Coupler (6ES7158-3MU10-0XA0) (All versions), SIMATIC PN/PN Coupler (6ES7158-3AD10-0XA0) (All versions < V6.0.0), SIPLUS ET 200MP IM 155-5 PN HF (6AG1155-5AA00-2AC0) (All versions >= V4.2.0), SIPLUS ET 200MP IM 155-5 PN HF (6AG1155-5AA00-7AC0) (All versions >= V4.2.0), SIPLUS ET 200MP IM 155-5 PN HF T1 RAIL (6AG2155-5AA00-1AC0) (All versions >= V4.2.0), SIPLUS ET 200SP IM 155-6 PN HF (6AG1155-6AU01-2CN0) (All versions >= V4.2.0 < V4.2.5), SIPLUS ET 200SP IM 155-6 PN HF (6AG1155-6AU01-7CN0) (All versions >= V4.2.0 < V4.2.5), SIPLUS ET 200SP IM 155-6 PN HF T1 RAIL (6AG2155-6AU01-1CN0) (All versions >= V4.2.0 < V4.2.5), SIPLUS ET 200SP IM 155-6 PN HF TX RAIL (6AG2155-6AU01-4CN0) (All versions >= V4.2.0 < V4.2.5), SIPLUS NET PN/PN Coupler (6AG2158-3AD10-4XA0) (All versions < V6.0.0). Affected devices do not properly handle S7 protocol session disconnect requests. When receiving a valid S7 protocol Disconnect Request (COTP DR TPDU) on TCP port 102, the devices enter an improper session state.
This could allow an attacker to cause the device to become unresponsive, leading to a denial-of-service condition that requires a power cycle to restore normal operation.
CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N
Productos afectados
Siemens · SIMATIC ET 200AL IM 157-1 PNSiemens · SIMATIC ET 200MP IM 155-5 PN HFSiemens · SIMATIC ET 200SP IM 155-6 MF HFSiemens · SIMATIC ET 200SP IM 155-6 PN/2 HFSiemens · SIMATIC ET 200SP IM 155-6 PN/3 HFSiemens · SIMATIC ET 200SP IM 155-6 PN HA (incl. SIPLUS variants)Siemens · SIMATIC ET 200SP IM 155-6 PN R1Siemens · SIMATIC PN/MF CouplerSiemens · SIMATIC PN/PN CouplerSiemens · SIPLUS ET 200MP IM 155-5 PN HFSiemens · SIPLUS ET 200MP IM 155-5 PN HF T1 RAILSiemens · SIPLUS ET 200SP IM 155-6 PN HFSiemens · SIPLUS ET 200SP IM 155-6 PN HF T1 RAILSiemens · SIPLUS ET 200SP IM 155-6 PN HF TX RAILSiemens · SIPLUS NET PN/PN Coupler