CVE-2025-40944: high-severity vulnerability in Siemens SIMATIC ET 200AL IM 157-1 PN
Published · Updated
E-mail alert when it lands in KEV, gets a public PoC or its score goes up.
21Vexday Risk Score
No sign of exploitation. No public exploitation artifact known so far.
ssvc Trackcvss 8.7epss 0.4%
A vulnerability has been identified in SIMATIC ET 200AL IM 157-1 PN (6ES7157-1AB00-0AB0) (All versions), SIMATIC ET 200MP IM 155-5 PN HF (6ES7155-5AA00-0AC0) (All versions >= V4.2.0), SIMATIC ET 200SP IM 155-6 MF HF (6ES7155-6MU00-0CN0) (All versions), SIMATIC ET 200SP IM 155-6 PN HA (incl. SIPLUS variants) (All versions < V1.3), SIMATIC ET 200SP IM 155-6 PN R1 (6ES7155-6AU00-0HM0) (All versions < V6.0.1), SIMATIC ET 200SP IM 155-6 PN/2 HF (6ES7155-6AU01-0CN0) (All versions >= V4.2.0 < V4.2.5), SIMATIC ET 200SP IM 155-6 PN/3 HF (6ES7155-6AU30-0CN0) (All versions < V4.2.2), SIMATIC PN/MF Coupler (6ES7158-3MU10-0XA0) (All versions), SIMATIC PN/PN Coupler (6ES7158-3AD10-0XA0) (All versions < V6.0.0), SIPLUS ET 200MP IM 155-5 PN HF (6AG1155-5AA00-2AC0) (All versions >= V4.2.0), SIPLUS ET 200MP IM 155-5 PN HF (6AG1155-5AA00-7AC0) (All versions >= V4.2.0), SIPLUS ET 200MP IM 155-5 PN HF T1 RAIL (6AG2155-5AA00-1AC0) (All versions >= V4.2.0), SIPLUS ET 200SP IM 155-6 PN HF (6AG1155-6AU01-2CN0) (All versions >= V4.2.0 < V4.2.5), SIPLUS ET 200SP IM 155-6 PN HF (6AG1155-6AU01-7CN0) (All versions >= V4.2.0 < V4.2.5), SIPLUS ET 200SP IM 155-6 PN HF T1 RAIL (6AG2155-6AU01-1CN0) (All versions >= V4.2.0 < V4.2.5), SIPLUS ET 200SP IM 155-6 PN HF TX RAIL (6AG2155-6AU01-4CN0) (All versions >= V4.2.0 < V4.2.5), SIPLUS NET PN/PN Coupler (6AG2158-3AD10-4XA0) (All versions < V6.0.0). Affected devices do not properly handle S7 protocol session disconnect requests. When receiving a valid S7 protocol Disconnect Request (COTP DR TPDU) on TCP port 102, the devices enter an improper session state.
This could allow an attacker to cause the device to become unresponsive, leading to a denial-of-service condition that requires a power cycle to restore normal operation.
CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N
Affected products
Siemens · SIMATIC ET 200AL IM 157-1 PNSiemens · SIMATIC ET 200MP IM 155-5 PN HFSiemens · SIMATIC ET 200SP IM 155-6 MF HFSiemens · SIMATIC ET 200SP IM 155-6 PN/2 HFSiemens · SIMATIC ET 200SP IM 155-6 PN/3 HFSiemens · SIMATIC ET 200SP IM 155-6 PN HA (incl. SIPLUS variants)Siemens · SIMATIC ET 200SP IM 155-6 PN R1Siemens · SIMATIC PN/MF CouplerSiemens · SIMATIC PN/PN CouplerSiemens · SIPLUS ET 200MP IM 155-5 PN HFSiemens · SIPLUS ET 200MP IM 155-5 PN HF T1 RAILSiemens · SIPLUS ET 200SP IM 155-6 PN HFSiemens · SIPLUS ET 200SP IM 155-6 PN HF T1 RAILSiemens · SIPLUS ET 200SP IM 155-6 PN HF TX RAILSiemens · SIPLUS NET PN/PN CouplerRelated CVEs — Siemens SIMATIC ET 200AL IM 157-1 PN
In the same product, most dangerous first.